Sizing of Installations
Basics of Sizing Applications
Air Changes per
Hour Method
Exhaust
Temperature Calculation – Heat Load
Exhaust
Temperature Calculation – Heat Load with Stratification
Spot Cooling
Basics of
Sizing Applications
There are a number of methods
determining the number of evaporative coolers required:
- A ventilation system based on
the number of air changes per hour
- Performing a heat balance on
the building to calculate exhaust temperature
- Spot cooling
In order do complete any
calculations both the temperature and the flow rate out of the
cooler must be calculated. The method of determining the cooler
outlet temperature is described in detail in Section 17. The flow
rate of the coolers is dependent on the fan curve and the air
distribution system. The principle of the calculation is shown
below.
|
The fan curve for an axial fan,
as fitted to all EcoCooling coolers, has the characteristic
curve as shown by the blue line. Air distribution systems have
a characteristic curve as shown by the green line.
By using the design
information from the air distribution system and the fan curve
given in the cooler specification the actual flow rate can be
established.
In this case an air flow rate
of just over 14,000m 3/hr (3.8m 3/s) is achieved at a static
pressure of 150Pa |
 |
Specialist advice must be taken
to establish the actual performance of the system.
Air Changes per
Hour Method
This method calculates the number
of coolers required based on the number of air changes per hour
with a given working volume.
The number of air changes per
hour required is based partially on experience and partially on
the typical values shown on the table in the next part of this
document.
The working volume is that
underneath the discharge of the plenum chambers as shown by the
blue shaded area in the diagram below.

Example
calculation:
A bakery is 20m x 24m and it is
proposed to fit ECP plastic external units with a minimum plenum
discharge height of 3.5m.
Volume of working area of the
building: 20 x 24 x 3.5 = 1680m 3
Target air changes per hour: 30
Target air flow per hour: 30 x
1680 = 50,400m 3/hr
Air flow rate of ECP16000 14,000
m 3/hr@150Pa
Nominal number of coolers
required 50,400 / 14,000 = 3.6 = 4 coolers
Therefore the proposal would be 4
ECP16000 coolers together with balanced extract to maintain a
small positive pressure.
Ventilation Rates with Air Velocities
Location Air
Changes Per Hour
Assembly Halls 4 – 8
Bakeries 20 – 30
Banks 4 - 8
Bathrooms 6 - 10
Bedrooms 2 - 4
Billiard Rooms * 6 - 8
Boiler Rooms 15 - 30
Cafes and Coffee Bars 10 - 12
Canteens 8 - 12
Cellars 3 - 10
Changing Rooms - Main area 6 - 10
Changing Rooms - Shower area 15 - 20
Churches 1 - 3
Cinemas and Theatres * 10 - 15
Club rooms 10 - 12
Compressor rooms 10 - 20
Conference rooms 8 - 12
Dance halls 8 - 12
Dental surgeries 12 - 15
Dye works 20 - 30
Electroplating shops 10 - 12
Engine rooms 15 – 30
Entrance Halls & Corridors 3 - 5
Factories and Workshops 8 - 10
Foundries 15 - 30
Garages (Showrooms) 6 - 8
Glasshouses 25 - 60
Gymnasiums 6 min
Hairdressing Salons 10 - 15
Hospitals - Sterilising 15 - 25
- Wards 6 - 8
Kitchens - Domestic 15 - 20
Commercial 20 -30
Laboratories 6 - 15
Launderettes 10 - 15
Laundries 10 - 30
Lavatories 6 - 15
Lecture theatres 5 - 8
Libraries 3 - 5
Living rooms 3 - 6
Mushroom Houses 6 - 10
Offices 6 - 10
Paint shops (not cellulose) 10 - 20
Photo & X-ray darkrooms 10 - 15
Public house bars 10 - 15
Recording studios 10 - 12
Recording Control rooms 15 - 25
Restaurants 8 - 12
Schoolrooms 5 - 7
Shops and Showrooms 8 - 15
Shower baths 15 - 20
Stores & warehouses 3 - 6
Swimming baths 10 - 15
Toilets 6 - 10
Utility rooms 15 - 20
Welding shops 15 - 30
Exhaust
Temperature Calculation – Heat Load
This calculation is based on
taking the ambient conditions of the air, calculating the
discharge temperature of the evaporative cooler, and then
performing an energy balance to achieve a target exhaust
temperature from the building.
Ambient temperature Ti °C
Ambient RH RH%
Discharge temperature from cooler Tc °C
Heat generated in building H KW
Target Air temperature out Te °C
Volumetric flow rate of Air V m 3/s
The temperature of the air Tc
leaving the evaporative cooler is found by using the psychrometric
chart using an adiabatic cooling efficiency of 85%.
The flow rate of air required to
meet the target exhaust temperature is then given by:
V=1.28H/(Te-Tc)
This flow rate can then be used
to select the type and numbers of coolers.
Example.
A target temperature of 27 °C is
required in a building which has a heat gain of 100KW. The
external conditions are 30 °C 35%RH.
Step 1 – Calculate the cooler
discharge temperature using the ambient conditions:
At 30 °C 35%RH and a pad
efficiency of 85% the discharge temperature from the evaporative
cooler is 20.7 °C
Step 2 – Calculate the air flow
rate required to maintain the target temperature:
Te=20.7°c
Tc=27.0 °C
H = 100KW
V =
0.78x100/(27.0-20.7)=78/6.3=12.4m 3/s
Therefore a total flow rate of
12.4m 3/s is required
Step 3 – Calculate the number of
coolers required:
An ECP16000@150Pa delivers 14,000
/ 3600 = 3.8m 3/s
Number of coolers 12.4 / 3.8 =
3.4 = 4 coolers
Exhaust
Temperature Calculation – Heat Load with Stratification
The previous method can be
further refined if a temperature stratification exists. If the
degree of stratification is known then a thermal balance can be
done to maintain a temperature at the lowest level in the
building.
Ambient temperature Ti °C
Ambient RH RHa%
Heat generated in building H KW
Target Air temperature at lower level Tl °C
Temperature differential Td
Temperature at high level (exhaust) Th
Heat generated in building H KW
Volumetric flow rate of Air V m 3/s
The temperature of the air Tc
leaving the evaporative cooler is found by using the psychrometric
chart using an adiabatic cooling efficiency of 85%.
The flow rate of air required to
meet the target exhaust temperature is then calculated using the
following equation:
Air flow = 0.78xH/(Tl+Td-Ti)
Example
A target temperature of 24 °C is
required in a building which has a heat load of 150KW. The ambient
conditions are 32 °C 30%RH. There is a 5 °C temperature
stratification in the building.
Step 1 – Calculate the discharge
temperature of the evaporative cooler. (See Section 17)
At 32 °C 30%RH and a pad
efficiency of 85% the discharge temperature from the evaporative
cooler is 21.2 °C
Step 2 – Calculate the flow rate
of air
V=(0.78 x
150)/(24+5-21.2)=117/7.8=15.0m 3/s
Step 3 – Calculate the number of
coolers require
An ECP16000@150Pa delivers
14,000/3600=3.8m 3/s
Number of coolers 15.0 / 3.8 =
3.9 = 4 coolers

Spot Cooling
Spot cooling is calculated based
on principles similar to the air changes per hour method. The
output from a cooler together with the discharge height of the air
can be used to understand the air changes per hour in a given
area. A design can then be done to reflect the operating
conditions.
A given volume of air discharged
at a given height will give the diameter of a circular area from a
given target number of air changes per hour to the following
calculation.
Height of discharge of air H m
Diameter of circular area D m
Cooler flow rate V m 3/hr
Air Changes per hour A
A = (4 x V)/(3.142xDxDxH)
D = sqrt((4xV)/(3.142xAxH))
Example
What diameter circle will achieve
25 air changes per hour with an ECP16000 producing 14000 m 3/hr
with a plenum discharge height of 3.5m?
V=14000
H = 3.5
A = 25
D = sqrt(4x14000)/(3.142x25x3.5)
= sqrt (56000/274.9) = sqrt (203.7) = 14.2m
|